Image
DC 1.1
Technical
Image
Adresse
202, Z.A.E. Wolser F,
L-3290 Bettembourg
L-3290 Bettembourg
Operational since
June 2009
- Uptime Tier IV certified
- 100% renewable energy sources
- Electromagnetic protection concept
- Remote central monitoring of all technical systems
Data Center information
Image
Gross size
10000.00m²
Net size
3100.00m²
Power available
2 x 6.3 MVA
IT Room height
3.80m
Raised floor
1.00m
Floor load
1500.00kg/m²
Equipment elevator
4000.00kg
UPS systems
Redundant 2 x (N+1)
Generator autonomy
48 hours; 24/365
refuel contracts
refuel contracts
Power to IT rooms
Average 1,150 W/m²
Power loads
up to 5 kW/rack
Server room temperature
18-27° C - ASHRAE TC9.9 Class A1 recommended
Cooling redundancy
2 x N
Cooling specifications
Water input 10° C;
output 15° C
output 15° C
PUE
1.45 / 1.5
SLA