Image
DC 2
Technical
Image
Adresse
3, op der Poukewiss, ZAC Klengbousbierg, L-7795 Bissen
Operational since
April 2012
- Uptime Tier IV certified
- 100% renewable energy sources
- Electromagnetic protection concept
Data Center information
Image
Gross size
21000.00m²
Net size
4800.00m²
Power available
2 x 12.6 MVA
IT Room height
3.80m
Raised floor
1.20m
Floor load
2000.00kg/m²
Equipment elevator
2500.00kg
UPS systems
-
Generator autonomy
48 hours; 24/365 refuel contracts
Power to IT rooms
Average = 1750 W/m²
Power loads
up to 10 kW/rack
Server room temperature
18-27° C - ASHRAE TC9.9 Class A1 recommended
Cooling redundancy
2 x N, N + 1
Cooling specifications
Water input 12° C; output 18° C
PUE
1,35
SLA
99.99%